SP C-275 V1 1-module SPD class 2
Description
- Combined surge protection devise Class 2
- Series FS SPARK C-275 with Uc=275 V
- Suitable for 1-phase AC network according to TN-C schemes with 2 wires:
phase (L1) + combined PEN
- Designed to protect distribution networks and connected equipment from the impact of induced impulse overvoltage during lightning strikes and from switching overvoltages.
- It’s installed in distribution boards between LPZ 1 – LPZ2 zones.
Construction:
- 1 module with varistor arrester based on Metal Oxide Varistor (MOV) technology
- Module replacement capability
- Visual + remote fault indication of the module
- TM “FS Lightning Protection” (Ukraine)
Connection according to 1+0 scheme:
- Phase wire (L1) to “L1” terminal on SPD
- Combined PEN wire to “PE” terminal on SPD
- Grounding bus to “PE” terminal on SPD
Features
| article | SP C-275 V1 |
|---|---|
| code | 810 809 |
| number of poles | 1 |
| SPD class | 2 (C) |
| AC system | 1-фазних TN-C (L1 + PEN) |
| Un | 230 V / 400V AC |
| Uc | 275 V AC |
| In | 30 kA |
| Imax | 60 kA |
| Up | 1,5 kV |
| Ures | 1,2 kV |
| If | 100 A |
| ta | 25 µs |
| protection rating | IP20 |
| Protection | 125 A gL/gG |
| Ut | 355 V / 5 sec |
| Operating temperature | -40C.. +80C |
| dimensions A1 x A2 | 90 x 18 mm |
| dimensions B1 x B2 x C | 64 x 49 x 35 mm |
| mounting | DIN рейка 35 мм |
| connecting | 1,5...25mm2 solid / 35mm2 flexible |
| price, uah | 1 236,00 |